Headquarters: Ashland, Massachusetts
FENWAL CONTROLS
Baumen Associates Ltd. proudly serves as the exclusive sales representative for Fenwal Controls, offering expert guidance and strategic market placement throughout Canada.
Our partnership provides access to a critical safety component for gas-fired equipment, including advanced gas valve controls, safe burner ignition, and continuous flame monitoring.
Fenwal Controls’ microprocessor technology ensures precise, repeatable timings and high dependability for both LP and natural gas appliances. Their platform products offer the benefits of custom design with the cost efficiency and availability of standard production units, including quick turn samples for agency approvals and responsive production ramp-up.
Explore our meticulously curated selection to enhance your application design and operational efficiency, and find the perfect solution tailored to your needs.
COMPONENTS
GAS IGNITION CONTROLS
At the heart of gas-fired appliances lies a critical safety component – a guardian that not only manages the gas valve with precision but also ensures the burner ignites safely and keeps a vigilant watch over the flame. In the rare event of a flame loss, it responds instantaneously to safeguard both equipment and surroundings. Fenwal Controls leverages advanced microprocessor technology to offer precise, consistent timings and unparalleled reliability for your appliance’s service life, whether utilizing LP or natural gas.
The innovative “platform” products merge the best of both worlds: the customization you desire, with the cost-effectiveness and ready availability typical of standard production units. This unique approach extends to “quick turn” samples, facilitating swift agency approvals and enabling a smooth transition to production scaling. Trust in Fenwal Controls solutions to elevate the safety, efficiency, and dependability of your gas-fired equipment.
Technical Features
- Gas Ignition Controls are the critical safety components of gas-fired equipment
- They control the gas valve, safely light the burner and continuously monitor the flame
- Responding instantly to a loss of flame, the ignition control will instantly cut power to the gas valve
- Fenwal Control’s microprocessor technology provides precise, repeatable timings and high dependability for the appliance service, whether it be LP or natural gas
- Fenwal “platform” products provide the benefit of custom design with the price and availability of standard production units
HOT SURFACE GAS IGNITION CONTROLS (HSI)
Technical Features
- Combustion blower output
- Proven pressure switch input
- 24/120/240 VAC hot surface ignitor models available
- ASME CSD-1 compatible models available (consult factory)
- Pre-purge and lockout indicator outputs
- Non-volatile lockout option
- Diagnostic LED and remote LED connection
- Multiple trials for ignition
- Thermostat, pushbutton or remote reset
- Full-time flame sensing
- Remote flame sensor option
- Flame current test pins
DIRECT SPARK GAS IGNITION CONTROLS (DSI)
Technical Features
- Safe start with DETECT-A-FLAME® flame sensing technology
- Single or three trials for ignition
- Green power LED
- System diagnostic LED
- Flame current test points
- Local or remote flame sensing
- Non-volatile lockout with manual reset (optional)
- Digital alarm output
- UART communications (optional)
- RoHs compliant
CONNECTED CONTROLS IOT PLATFORM
Technical Features
- Input Power and Current: 24VAC @ 200mAmps, 24VDC @ 200mAmps and 12VDC @ 200mAmps
- Operating Temperature: 40°F to +176°F (-40°C to +80°C)
- Storage Temperature: -40°F to +185°F (-40°C to +85°C)
- UART Communication: 5V TTL or 3.3V RS485
- Thermostat Input: 12/24VDC, 24/120VAC
- Proving Switch 1: 12/24VDC, 24/120VAC
- Proving Switch 2 & 3 12VDC, 24VAC/AC
- Moisture Resistance: 95% RH non-condensing
Additional options include:
- Internal or external antenna
- TTL or RS 485 communications
- Customized software
PLATFORM IGNITION MODULE (PIM)
Technical Features
- Input Power Control: 18-30 VAC 50/60 Hz (Class 2 Transformer)
- Input Current Drain: 400 mA @ 24 VAC with gas and blower relays energized (Control only)
- Gas Valve Relays: 5.0A max (continuous) Combustion Blower 5.0 A max for standard (J2) connection 15.0 A max for heavy-duty (K5 relay) terminals
- Hot Surface Igniter: 5.0 A max, 120/240 VAC Pump Relays 5.0 A max (continuous)
- Alarm Relay: 2.0 A, 30 VDC or 30 VAC max
- Operating Temperature: -40°F to + 165°F (-40°C to +74°C)
- Storage Temperature: -40°F to + 185°F (-40°C to +85°C)
- Sensor Temperature Range: -22°F to + 260°F (-30°C to +126°C)
- Flame Sensitivity: 0.7 μA minimum
- Flame Failure Response or Reignition: Time 0.8 seconds maximum
- Flame Detector Self-check Rate: Once per second minimum